There are two limit switches and a limit rotor in each operator. The function of these is to stop the operators turning when the limit switch is struck by the rotor which is attached to the main shaft.Before setting up the limit switches you have to establish the closing direction of the operators. The operators should automatically drive to the closed position when first powered up but as each site is unique it may not. Apply power to the motor and take note of the direction that the shaft turns. NOTE: If it is determined that the operators are turning the correct way, continue to set up the limit switches as shown below.If the operators are turning the incorrect way you must reverse the motor wires. Follow the instruction below before continuing to set up the limit switches. Remove the power. Reverse the motor wires at the limit diodes as shown above. 8. Tighten the rotor . Do not over tighten. The limit switch When connecting any auxiliary equipment to the PC Board ensure that all power is removed A DuraTronic external receiver can be connected to the PC Board. This will be necessary if there are more than 15 remotes to be used or if the range of the on-board receiver is not sufficient.The DuraTronic external receiver can hold 128 remotes. The DuraTronic receiver should be mounted outside the operator housing for increased range. When connecting any auxiliary equipment to the PC Board ensure that all power is removed A DuraTronic external receiver can be connected to the PC Board. PEDESTRIAN OPERATION: A separate receiver, keyswitch or keypad must be connected to operate In pedestrian mode the gate will open partially and then close automatically after 6 seconds Note: although the installation of infrared safety beams does reduce the risk of the gate
The operators should be running in the correct direction i.e. when the CLOSE LED is on the gates must be closed and when the OPEN LED is on the gates must be open. Now proceed to set up the limit switches.
1. Stand the battery up in a vertical position to allow for access to the limit rotor
2. Apply the battery power. The operators will automatically turn until the closed limit
is struck.
3. Before tightening the crank arms ensure that the gates are set up correctly using the diagrams on pages 11 –15. The gates must now be placed in the closed position and
the crank arms can now be tightened. (23mm spanner.)
4. Loosen the limit rotor . The rotor is a black plastic cam shaped rotor. The rotor
can be removed completely to assist with the set-up
5. Press the test button on the PC Board. The gates will now start opening.
6. When gate reaches the required open position, press the limit switch.
This is made easier using a small flat screwdriver. The motor will stop.
The limit switch can be released when the operators have stopped running.
7. Lift and turn the rotor until it presses on the limit switch.
Hits: 229
from the PC Board.
Hits: 114
from the PC Board.
the gate in the pedestrian mode. The connection is done in the same manner as the diagram above with the exception of the TRIG connection. Instead of TRIG to N/O it must be PED on the main PC Board to N/O.
Hits: 102
striking an object while closing it does not guarantee against it.
Hits: 101
Dace Dura Swing Motor
1.Dace Dura Swing
All about the Dace Dura-Swing Motor
Gensix Technical26-04-2021
Was this helpful?00
Gensix Technical26-04-2021
Was this helpful?10
Gensix Technical26-04-2021
Was this helpful?10
Gensix Technical26-04-2021
Was this helpful?00